Back

ATX124 - Safety Circuit Module

Safety circuit module ATX124 was designed as intrinsically safe module. It provides monitoring of parametric safety circuit, which status reflects on status of output contacts of the module. The device provides SIL 4 degree of functional safety according to PN-EN 61508 norm in range of temperatures from 0 to 40°C and SIL 3 in range of temperatures from 0 to 70°C. Because of type of implemented intrinsically safe construction, there is version ATX124/12 (for supply voltage 9,5 to 13 V) and ATX124/15 (for supply voltage 12,5 to 15 V). The construction of module meets the requirements of IEC61131 norm in range of standarization of functional and operational features and programming process. To keep appropriate intrinsically safe feature, the module should be build in casing with at least IP54 protection degree and meeting the requirements of EN 60079-11:2012 norm.

Technical data

ATEX certificate number FTZÚ 07 ATEX 0346X
Supply parameters:
Supply voltage U
- for version ATX124/12 9,5 ÷ 13 VDC
- for version ATX124/15 12,5 ÷ 15 VDC
Maximum Supply voltage U
- for version ATX124/12 13,8 VDC
- for version ATX124/15 15,8 VDC
Supply current I
-for version ATX124/12 < 130 mA
- for version ATX124/15 < 120 mA
PFHD 5,5 ∙ 10-9
Normal working conditions:
Casing type
in device with casing protection degree Ip54 I M1 Ex ia I Ma
in device with flameproof casing I (M1) [Ex ia Ma] I
Environment temperature:
- for SIL 3 0 ÷ 70°C
- for SIL 4 0 ÷ 40°C
Air humidity max 95%

Documents to download

1,55 MB en-atx124.pdf Download Download
European funds